| 2002-07-22 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) COMMENTS FROM PREVIOUS REVIEW NOT |
| | ADDRESSED. |
| | 2) SHT A1-1 ROOM #332, SHOWER BATHROOM |
| | SHALL BE ADAPTABLE. 11-4.1.3(11) PLEASE |
| | PROVIDE DETAILS. |
| | 3) SHT A1-1 SEPARATE TENANTS, MINIMUM |
| | FACILITIES REQUIRE A DRINKING FOUNTAIN |
| | AND SERVICE SINK. SERVICE SINK NOT FOUND |
| | IN TENANT "B" SPACE, AND DRINKING FOUNT- |
| | AINS NOT FOUND IN SPACE "A" OR "B". |
| | 4) SHT A2-1 DETAILS #7 RM #312 & #16 RM |
| | #345, SINKS SHALL COMPLY WITH 11-4.24 |
| | AND ALL SUBSECTIONS. PROVIDE DETAILS. |
| | 5) SHT P1-3 FLOOR DRAIN AT WATER HEATER |
| | NOT APPROVED. ALL INDIRECT WASTE SHALL |
| | DRAIN INTO A FLOOR SINK. SEC 802.3 |
| | 6) SHT P2-1 MANUFACTURE INFORMATION RE- |
| | QUIRED FOR FILTER. MUST BE NSF APPROVED. |
| | 7) HEATER PAN REQUIRED SEC. 504.8 |
| | 8) BACKFLOW REQUIRED ON WATER SERVICE. |
| | 9) BACKFLOW REQUIRED FOR 3/4" LINE TO |
| | LASIK MACHINE. |
| | 10) WATER RISER DIAGRAM REQUIRED. WATER |
| | HAMMER ARRESTORS ARE REQUIRED FOR QUICK |
| | CLOSING VALVES. 604.9 - LOCATE NEAR FIX- |
| | TURE NOT AT TOP OF DROP. |
| | 11) THERMAL EXPANSION CONTROL REQUIRED |
| | PER SEC 607.3 & 607.3.2. SHOW ON HEATER |
| | DETAIL. |
| | 12) SANITARY RISER DIAGRAM REQUIRED FOR |
| | ENTIRE BLDG. SHOW FIXTURE UNITS FOR EACH |
| | RISER AS IT ACCUMULATES IN DRAIN. |
| | |
| | REVIEW BY KEN STEVENS |