2002-07-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED.
 2) SHT A1-1 ROOM #332, SHOWER BATHROOM
 SHALL BE ADAPTABLE. 11-4.1.3(11) PLEASE
 PROVIDE DETAILS.
 3) SHT A1-1 SEPARATE TENANTS, MINIMUM
 FACILITIES REQUIRE A DRINKING FOUNTAIN
 AND SERVICE SINK. SERVICE SINK NOT FOUND
 IN TENANT "B" SPACE, AND DRINKING FOUNT-
 AINS NOT FOUND IN SPACE "A" OR "B".
 4) SHT A2-1 DETAILS #7 RM #312 & #16 RM
 #345, SINKS SHALL COMPLY WITH 11-4.24
 AND ALL SUBSECTIONS. PROVIDE DETAILS.
 5) SHT P1-3 FLOOR DRAIN AT WATER HEATER
 NOT APPROVED. ALL INDIRECT WASTE SHALL
 DRAIN INTO A FLOOR SINK. SEC 802.3
 6) SHT P2-1 MANUFACTURE INFORMATION RE-
 QUIRED FOR FILTER. MUST BE NSF APPROVED.
 7) HEATER PAN REQUIRED SEC. 504.8
 8) BACKFLOW REQUIRED ON WATER SERVICE.
 9) BACKFLOW REQUIRED FOR 3/4" LINE TO
 LASIK MACHINE.
 10) WATER RISER DIAGRAM REQUIRED. WATER
 HAMMER ARRESTORS ARE REQUIRED FOR QUICK
 CLOSING VALVES. 604.9 - LOCATE NEAR FIX-
 TURE NOT AT TOP OF DROP.
 11) THERMAL EXPANSION CONTROL REQUIRED
 PER SEC 607.3 & 607.3.2. SHOW ON HEATER
 DETAIL.
 12) SANITARY RISER DIAGRAM REQUIRED FOR
 ENTIRE BLDG. SHOW FIXTURE UNITS FOR EACH
 RISER AS IT ACCUMULATES IN DRAIN.
  