| 2002-07-25 00:00:00 | DENIED:2ND REQUEST | | | | | | REFERENCE PLAN REVIEW BY NANCY DENMARK | | | DATED 5/30/02. | | | | | | ITEM #3 - PROVIDE OUTSIDE ARI CALCS AS | | | PER ASHRAE 62-89.PLEASE INDICATETHE | | | NUMBER OF PEOPLE PER AREA TO VERIFY THE | | | AMOUNT OF OUTSIDE AIR PROVIDED. | | | | | | ITEM #4 - FAN SHUTDOWN BY DUCT SMOKE | | | DETECTOR TO BE TESTED.PLEASE IDENTIFY | | | LOCATION OF ALL DUCT SMOKE DETECTORS ON | | | THE PLAN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|