Plan Review Notes
Plan Review Notes For Permit 02050144
Permit Number 02050144
Review Stop B
Sequence Number 2
Notes
Date Text
2002-07-15 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02050144
 ADD: 2505 W METROCENTE
 CONT: PROJECT CONTROL
 TEL: (561) 445-8588
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SEE TABLE 705.1.2 EXIT DOORS 302 &
 304 REQUIRE 1HR PROTECTIVE.
  
 2) MISSING INFORMATION ON TENANT ACCESS
 CORRIDOR DOORS, DOOR #, AND RATING.
  
 3) THE LARGE SUITE INDICATES SIDELITES
 BETWEEN THE DOUBLE FRONT DOORS, THERE IS
 NO INFORMATION ON THE WINDOW PROTECTIVES
  
 4) NOTE: TABLE 705.1.2 NOTE 6 SEE EXEMPT
 IONS UNDER BUILD FOR RATING OF RESTROOM
 DOORS PROVIDED (A-D)
  
 5) ROOM 332 SHOWER SHALL REQUIRE SAFETY
 GLASS IN SWING DOOR, HAZARDOUS LOCATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026