Plan Review Notes
Plan Review Notes For Permit 02050144
Permit Number 02050144
Review Stop P
Sequence Number 1
Notes
Date Text
2002-06-03 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A1-1 ROOM #332, SHOWER BATHROOM
 SHALL BE ADAPTABLE. 11-4.1.3(11) PLEASE
 PROVIDE DETAILS.
 2) SHT A1-1 SEPARATE TENANTS, PLEASE
 PROVIDE MINIMUM FACILITIES CALCULATIONS
 FOR EACH TENANT SPACE. PROVIDE SQUARE
 FOOTAGE FOR EACH SPACE SO FIXTURES CAN
 BE CALCULATED. DRINKING FOUNTAINS AND
 SERVICE SINKS REQUIRED ECT.
 3) SHT A2-1 DETAILS #7 RM #312 & #16 RM
 #345 SINKS SHALL COMPLY WITH 11-4.24 AND
 ALL SUBSECTIONS.
 4) SHT A1-1 TOILET ROOM #314, DOOR SHALL
 NOT OPEN INTO THE CLEAR FLOOR SPACE OF
 ANY FIXTURE. 11-2.22.2
 5) SHT P1-3 FLOOR DRAIN AT WATER HEATER
 NOT APPROVED. ALL INDIRECT WASTE SHALL
 DRAIN INTO A FLOOR SINK. SEC 802.3
 6) SHT P2-1 MANUFACTURE INFORMATION RE-
 QUIRED FOR THE POINT OF USE WATER HEATER
 FOR LISTING BY APPROVED AGENCY.
 7) SHT P2-1 MANUFACTURE INFORMATION RE-
 QUIRED FOR FILTER. MUST BE NSF APPROVED.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377