Plan Review Notes
Plan Review Notes For Permit 02050144
Permit Number 02050144
Review Stop M
Sequence Number 1
Notes
Date Text
2002-05-30 00:00:00DENIED:
 1) FLOOR PLAN A1-1 INDICATES TWO SPACES
 SEPARATED BY RATED PARTITION. MECH PLAN
 HAS FIRE DAMPER LOCATIONS NOT IN RATED
 WALL PER THE FLOOR PLAN. PLEASE SHOW
 FIRE DAMPERS IN ALL DUCTS PENETRATING
 RATED WALLS.
 2) WHERE IS VAV- 2-2?
 3) PROVIDE OUTSIDE AIR CALCULATIONS FOR
 EACH SPACE PER ASHRAE 62-89 OR TABLE
 403.3 FMC
 4) FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 TO BE TESTED.
  
 NANCY DENMARK
 CHIEF MECHANICAL INSPECTOR
 (561) 659-8096 EXT 8221