| Plan Review Notes For Permit 02050144 |
| Permit Number |
02050144 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-30 00:00:00 | DENIED: | | | 1) FLOOR PLAN A1-1 INDICATES TWO SPACES | | | SEPARATED BY RATED PARTITION. MECH PLAN | | | HAS FIRE DAMPER LOCATIONS NOT IN RATED | | | WALL PER THE FLOOR PLAN. PLEASE SHOW | | | FIRE DAMPERS IN ALL DUCTS PENETRATING | | | RATED WALLS. | | | 2) WHERE IS VAV- 2-2? | | | 3) PROVIDE OUTSIDE AIR CALCULATIONS FOR | | | EACH SPACE PER ASHRAE 62-89 OR TABLE | | | 403.3 FMC | | | 4) FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | TO BE TESTED. | | | | | | NANCY DENMARK | | | CHIEF MECHANICAL INSPECTOR | | | (561) 659-8096 EXT 8221 |
|