| Notes |
| Date |
Text |
| 2002-05-14 00:00:00 | 1) DESIGN CRITERIA FOR FIRE SPRINKLER | | | REMODEL NOTED ON PAGE F1-1 IS INCORRECT. | | | IT SHOULD READ NFPA 13, 1999 EDITION. | | | | | | 2) PLEASE EXPLAIN EXITING RATIONALE FOR | | | LARGE SPACE LOCATED ON THE THIRD FLOOR. | | | EXIT DOORS DO NOT APPEAR TO BE PROPERLY | | | SEPARATED FROM ONE ANOTHER. A SINGLE | | | FIRE COULD BLOCK BOTH EXITS. DURING THE | | | PLAN REVIEW FOR THE SHELL, CITY STAFF | | | EXPRESSED CONCERNS ABOUT FUTURE EXITING | | | FROM THE TENANT SPACES. | | | | | | 3) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR THE | | | WALLS AND CEILINGS. | | | | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM REMODELS WITHIN | | | THE TENANT SPACES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|