Plan Review Notes
Plan Review Notes For Permit 02050144
Permit Number 02050144
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-05-14 00:00:001) DESIGN CRITERIA FOR FIRE SPRINKLER
 REMODEL NOTED ON PAGE F1-1 IS INCORRECT.
 IT SHOULD READ NFPA 13, 1999 EDITION.
  
 2) PLEASE EXPLAIN EXITING RATIONALE FOR
 LARGE SPACE LOCATED ON THE THIRD FLOOR.
 EXIT DOORS DO NOT APPEAR TO BE PROPERLY
 SEPARATED FROM ONE ANOTHER. A SINGLE
 FIRE COULD BLOCK BOTH EXITS. DURING THE
 PLAN REVIEW FOR THE SHELL, CITY STAFF
 EXPRESSED CONCERNS ABOUT FUTURE EXITING
 FROM THE TENANT SPACES.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE
 WALLS AND CEILINGS.
  
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM REMODELS WITHIN
 THE TENANT SPACES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910