| 2002-05-15 00:00:00 | BUILDING PLAN REVIEW |
| | PRMIT# 02050144 |
| | 2505 W METROCENTRE BLVD |
| | CONT: PROJECT CONTROLS OF FL |
| | TEL:(305) 637-8000 |
| | |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | 2)1004.1.4 WHERE 2 OR MORE EXITS OR |
| | EXIT ACCESS DOORS ARE REQUIED, AT LEAST |
| | 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL |
| | BE PLACED A DISTANCE APART EQUAL TO NOT |
| | LESS THAN 1/2 OF THE LENGTH OF THE MAX- |
| | IMUM OVERALL DIAGONAL DIMENSION OF THE |
| | BUILDING OR AREA TO BE SERVED. |
| | 2001 FL BLD CODE ALLOWS FOR 1/3RD THE |
| | DISTANCE FOR SPRINKLERED BUILDINGS. THE |
| | LARGER OF THE 2 OFFICES HAS 16' BETWEEN |
| | THE EGRESS DOORS, 32.33' IS REQUIRED. |
| | IF BOTH UNITS ARE CONSIDERED AS ONE |
| | LARGE UNIT SINCE THERE IS A ADJOINING |
| | DOOR THE DIAGONAL DISTANCE IS 128' |
| | REQUIRING 42.66' BETWEEN EGRESS OPENINGS |
| | |
| | 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 4)11-4.1.3(1) AT LEAST ONE ACCESSIBLE |
| | ROUTE COMPLYING WITH 11-4.3 SHALL |
| | CONNECT ACCESSIBLE BUILDING OR FACILITY |
| | ENETRANCES WITH ALL ACCESSIBLE SPACES |
| | AND ELEMENTS WITHIN THE BUILDING OR |
| | FACILITY. SEE 4.13.6 FOR THE FOLLOWING |
| | DOORS: |
| | 336A EXT SIDE |
| | 336B INT SIDE |
| | 34345 DEGREE ANGLE DOESN'T GIVE THE |
| | REQUIRED CLEARENCES |
| | |
| | 5) RESTROOMS 314 THE CONFIGURATION ISNOT |
| | CORRECT NOR INSWING DOOR.4.22.2 DOORS |
| | SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE REQUIRED FOR ANY FIXTURE. SEE FIG- |
| | URE 28 FOR THE ENTRY FOR WATER CLOSETS |
| | ANY QUESTIONS PLEASE CALL, |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | DEPARTMENT OF CONSTRUCTION SERVICES |
| | CITY OF WEST PALM BEACH |
| | (561) 659-8096 EXT. 8412 |
| | OT |