| Plan Review Notes For Permit 02050091 |
| Permit Number |
02050091 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-15 00:00:00 | PROVIDE THE FOLLOWING INFORMATION WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | PROVIDE INFORMATION FOR EQUIPMENT BEING | | | INSTALLED (MAKE, MODEL, BTU, SEER ETC) | | | | | | PLEASE NOTE MAXIMUM DEVELOPED LENGTH FOR | | | THE DRYER EXHAUST SHALL NOT EXCEED 25 | | | FT FROM DRYER LOCATION TO OUTLET WITH A | | | 5 FT REDUCTION FOR EA 90 DEGREE BEND & | | | 2 1/2 FT REDUCTION FOR EA 45 DEGREE | | | BEND. 2001 FBC(M) 504.6. | | | | | | PROVIDE A BACKDRAFT DAMPER AS PER 2001 | | | FBC(M) 504.4. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|