2002-05-03 00:00:00~~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,REVISE THE PLANS AS
 NECESSARY AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 2} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.& ART
 210-52(A)(1)&(2).
  
 3} SHOW LOAD CALC'S FOR ANY ADDED LOADS.
  
 4} INDICATE LOCATION OF WASHER & DRYER
 RECEPTACLES.
  
 5} PLEASE NOTE ARTICLE 210-12,ARC FAULT
 REQUIREMENTS FOR BEDROOMS.
  
 6} SHOW HOW THE PERMIT VALUATION WAS DET
 ERMINED,PER 104.6.5,CWPB AMMENDMENTS.
  
  
 BILL TROBAUGH