| Plan Review Notes For Permit 02050078 |
| Permit Number |
02050078 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-03 00:00:00 | ~~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~ | | | | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,REVISE THE PLANS AS | | | NECESSARY AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 2} PLEASE NOTE KITCHEN COUNTER- | | | -SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5.& ART | | | 210-52(A)(1)&(2). | | | | | | 3} SHOW LOAD CALC'S FOR ANY ADDED LOADS. | | | | | | 4} INDICATE LOCATION OF WASHER & DRYER | | | RECEPTACLES. | | | | | | 5} PLEASE NOTE ARTICLE 210-12,ARC FAULT | | | REQUIREMENTS FOR BEDROOMS. | | | | | | 6} SHOW HOW THE PERMIT VALUATION WAS DET | | | ERMINED,PER 104.6.5,CWPB AMMENDMENTS. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 |
|