| Plan Review Notes For Permit 02050028 |
| Permit Number |
02050028 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-23 00:00:00 | PRIVISO | | | #1 NEED DUCT SIZE,CFM,GRILL SIZE,FOR | | | GUEST BATHROOM | | | #2 VARIFY TYPE OF VENTILATION FOR | | | FRESH AIR USED | | | #3 CALCULATION FOR TYPE OF VENTILATION | | | USED NATURAL 402 OR MECHANICAL 403 | | | #4 FAN SHUTDOWN REQUIRED FOR FINAL | | | INSPECTION | | | PLAN REVIEW BY HAROLD MOSER | | | [561]659-8096 EXT.8390 |
|