| 2002-05-25 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) ROUTE PLANS TO DEPT OF BUSINESS REGU- |
| | LATION HOTEL AND RESTAURANT DIVISION FOR |
| | REVIEW BEFORE RESUBMITTING TO WPB REVIEW |
| | 2) SHT A-5/5 SANITARY RISER DIAGRAM, |
| | SAMPLE POINT REQUIRED FOR 3 COMPARTMENT |
| | SINK, FLOOR DRAINS (WORK AREA), AND MOP |
| | SINK. AFTER THESE FIXTURES INSTALL SAM- |
| | PLE POINT. AFTER SAMPLE POINT TIE INTO |
| | SANITARY DRAIN. |
| | 3) SHT A-5/5 HUB DRAIN NOT APPROVED FOR |
| | INDIRECT WASTE. (ICE/SODA MACHINE) FLOOR |
| | SINK REQUIRED FOR ALL INDIRECT WASTE. |
| | SEC 802.3 |
| | 4) SHT A-5/5 WATER FILTRATION SYSTEM |
| | SHALL BE NSF APPROVED. PLEASE PROVIDE |
| | MANUFACTURE INFORMATION. |
| | 5) SHT A5/5 DRINKING FOUNTAIN REQUIRED |
| | TABLE 403.1. ALSO SEE 410.1 BOTTLED |
| | WATER REQUIREMENT ARI-1010, IF USED SUB- |
| | MIT MANUF. INFO SHOWING COMPLIANCE. |
| | 6) SHT A-1/5 MINIMUM SIZE OF HDCP TOILET |
| | ROOM SHALL BE 5'3". 5'2" SHOWN |
| | 7) SHT A-5/5 PLUMBING NOTES #4 AIR CHAM- |
| | BERS ARE NOT APPROVED. LOCATE WATER HAM- |
| | MERS NEAR FIXTURES IN AN "EFFECTIVE |
| | RANGE" NOT AT TOP OF DROPS. |
| | 8) RPZ BACKFLOW REQUIRED ON WATER SERV- |
| | ICE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |