Plan Review Notes
Plan Review Notes For Permit 02050026
Permit Number 02050026
Review Stop P
Sequence Number 1
Notes
Date Text
2002-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) ROUTE PLANS TO DEPT OF BUSINESS REGU-
 LATION HOTEL AND RESTAURANT DIVISION FOR
 REVIEW BEFORE RESUBMITTING TO WPB REVIEW
 2) SHT A-5/5 SANITARY RISER DIAGRAM,
 SAMPLE POINT REQUIRED FOR 3 COMPARTMENT
 SINK, FLOOR DRAINS (WORK AREA), AND MOP
 SINK. AFTER THESE FIXTURES INSTALL SAM-
 PLE POINT. AFTER SAMPLE POINT TIE INTO
 SANITARY DRAIN.
 3) SHT A-5/5 HUB DRAIN NOT APPROVED FOR
 INDIRECT WASTE. (ICE/SODA MACHINE) FLOOR
 SINK REQUIRED FOR ALL INDIRECT WASTE.
 SEC 802.3
 4) SHT A-5/5 WATER FILTRATION SYSTEM
 SHALL BE NSF APPROVED. PLEASE PROVIDE
 MANUFACTURE INFORMATION.
 5) SHT A5/5 DRINKING FOUNTAIN REQUIRED
 TABLE 403.1. ALSO SEE 410.1 BOTTLED
 WATER REQUIREMENT ARI-1010, IF USED SUB-
 MIT MANUF. INFO SHOWING COMPLIANCE.
 6) SHT A-1/5 MINIMUM SIZE OF HDCP TOILET
 ROOM SHALL BE 5'3". 5'2" SHOWN
 7) SHT A-5/5 PLUMBING NOTES #4 AIR CHAM-
 BERS ARE NOT APPROVED. LOCATE WATER HAM-
 MERS NEAR FIXTURES IN AN "EFFECTIVE
 RANGE" NOT AT TOP OF DROPS.
 8) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377