| Notes |
| Date |
Text |
| 2002-05-15 00:00:00 | ****************** UNSAT ************* | | | | | | 1 )NOTE: PLEASE NOTE THAT THE LOAD | | | CALCULATIONS NEED TO BE SHOWN. SQ FT/ | | | RECEPT LOADS ETC. PER 220-3,220-10, | | | 220-11, 220-13. (215-5) | | | | | | 2) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) | | | 215-2,215-3,230-42 | | | | | | 3)NOTE: PLEASE CORRELATE PANEL SCHEDULES | | | W/ RISER DIAGRAM. ONE SHOWS NEW B AND | | | OTHER NEW A ?? | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THEREARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|