Plan Review Notes
Plan Review Notes For Permit 02050026
Permit Number 02050026
Review Stop B
Sequence Number 1
Notes
Date Text
2002-05-30 00:00:005/30/02 MEET WITH ARCH TODAY, WILL
 PROVISO, LETTER SHALL BE REQUIRED STAT-
 ING THAT THE 2ND FLOOR WILL NOT BE USED,
 THE STAIRS WILL BE REMOVED, ELECTRIC
 AND MECHICAL WILL BE REMOVED AND THE
 DOORWAY WALLED UP. THE FLOOR/CEILING
 ASSEMBLY REPLACED TO SATISFY THE
 REQUIRED RATING.
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412
 R
2002-05-15 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW# 02050026
 124 N DIXIE
 CONT: INTERNATIONAL CONSTRUCTION
 TEL: (305) 867-8127
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2)1004.1.2 EVERY ROOM OR TENANT SPACE
 SHALL BE PROVIDED WITH A MINIMUM OF ONE
 MEANS OF EGRESS. PLANS INDICATE A SECOND
 FLOOR ABOVE AND THE REMOVAL OF A STAIR-
 WELL. IS THERE EGRESS FROM A NOTHER
 RATED STAIR? IS THE REMOVAL OF THIS
 STAIR A MEANS OF EGRESS OR A SECONDARY
 STAIRWAY?
 MEANS OF EGRESS: A CONTINUOUS AND
 UNOBSTRUCTED WAY OF TRAVEL FROM ANY
 POINT IN A BUILDING OR STRUCTURE TO A
 PUBLIC WAY, CONSISTING OF THREE SEPERATE
 AND DISTINCT PARTS: (1) THE WAY OF THE
 EXIT ACCESS, (2) THE EXIT, AND (3) THE
 THE WAY OF OF THE EXIT DISCHARGE.
 A MEANS OF EGRESS COMPRISES THE VERTICAL
 AND HORIZONTAL WAYS OF TRAVEL AND
 INCLUDE THE INTERVENING ROOM SPACE,DOORS
 CORRIDORS,PASSAGEWAYS,BALCONIES, STAIRS,
 RAMPS, ENCLOSURES, LOBBIES, HORIZONTAL
 EXITS, COURTS AND YARDS.
  
 3)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 4) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412