| | BUILDING PLAN REVIEW |
| | PERMIT: 02041956 |
| | ADD: LOT# 47 SEC.# 5 RENASSANCE |
| | CONT: HOME DYNAMICS CONST CORP |
| | TEL: (954)275-8569 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1)FL BLDG 1909.3 (EXEPTION# 2) |
| | CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| | PORTED BY APPROVED MATERIALS OR SUPPORTS |
| | AT SPACING NOT TO EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURER'S SPEC. |
| | |
| | 2)1804.1.3 THE BOTTOM OF THE FOUNDA- |
| | TION SHALL EXTEND NO LESS THAN 12" |
| | BELOW FINISH GRADE. SHEET A-4, TYPICAL |
| | WALL SEC NOTE 1821.1.1 IS FOR "HIGH WIND |
| | AREAS". |
| | |
| | 3) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | THE REPORT SUBMITTED INDICATES ON PAGE |
| | 9 "THE INFORMATION PROVIDED IN THIS |
| | REPORT IS NOT SUFFICIENT FOR A FINAL |
| | DESIGN OF THE FOUNDATION SYSTEM. |
| | |
| | 4) SHEET A-1 BOTTOM RIGHT OF CENTER, |
| | DISSCREPAANCY, PLANS CONFORM TO 2001 FBC |
| | / ASCE 5-95, SHOULD READ 7-98. |
| | |
| | 5) PLANS INDICATE CHANGES IN BLACK INK, |
| | QUESTIONABLE AS TO WHOS CHANGES THESE |
| | ARE, PRESSURE ZONES ARE ALSO ADDED WITH |
| | OUT ARCHITECTS INITIALS OR ACCOMPANYING |
| | SIGNED / SEALED LETTER. |
| | |
| | 6) COPY OF ASSOCIATIONS COVENENT, ROOF |
| | LINE IS OVER ZERO-LOT LINE? |
| | |
| | 7) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED.MISSING REPORTS: |
| | A) ROOFING REPORT; PROVIDE CURRENT |
| | ROOFING ASSEMBLY REPORT. |
| | B) GARAGE DOOR, HIGHLIGHT WHICH MODEL |
| | C) FRONT ENTRY DOOR. |
| | D) GLASS BLOCK, TO BE 1 HOUR RATED!!! |
| | THE GLASS BLOCK IS LOCATED IN THE ZERO- |
| | LOT LINE SIDE WHICH REQUIRES A HOUR RAT- |
| | ING WITH NO OPENINGS. |
| | E) 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 8)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | 9)1707.4.4.1 ANCHOR REQUIREMENTS: |
| | WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR |
| | ED IN ACCORDANCE WITH THE PUBLISHED |
| | MANUFACTURER'S RECOMMENDATIONS TO |
| | ACHIEVE THEDESIGN PRESSURE SPECIFIED. |
| | SUBSTITUTE ANCHORING SYSTEM USED FOR |
| | THE SUBSTRATE NOT SPECIFIED BY THE |
| | FENESTRATION MANUFACTURER SHALL PROVIDE |
| | EQUAL OR GREATER ANCHORING AS DEMONSTRA- |
| | TED BY ACCEPTED ENGINEERING PRACTICES. |
| | SHEET A-4 DETAILS INDICATE A DIFFERENT |
| | METHOD OF ATTACHMENT THAN SPECIFIED BY |
| | THE PRODUCT APPROVAL CHECK ALL REPORTS |
| | VS DETAILS! |
| | |
| | 10)FL BLD CODE CHAP 13 ENERGY EFFICENCY |
| | PROVIDE ENERGY CALS/ W MANUAL "J" |
| | |
| | 11) SHEET A-2 ROOF FRAMING PLAN, DOES |
| | NOT PROVIDE THE MAGNITUDE OF FORCES THAT |
| | ARE TO BE RESISTED, VERTICAL, HORIZONTAL |
| | OR GRAVITY. |
| | |
| | 12) TRUSS ANCHOR SCHEDULE NOT INCLUDED, |
| | INDICATE MANUFACTURER, AND MODEL, DELETE |
| | ALL NOTES OF SEMCO AND HUGHES, THESE |
| | MANUFACTURERS ARE NO LONGER IN BUSINESS. |
| | |
| | 13) SHEET A-4 NO INDICATION AS TO WHAT |
| | TYPE OF LATH IS TO BE USED FOR THE |
| | STUCCO SOFFIT, FBC 2405.2.2: |
| | 2504.2.2 INSTALLATION OF EXTERIOR |
| | LATHING AND FRAMING SHALL COMPLY WITH |
| | ASTM C-1063. IF RIB LATH IS TO BE USED |
| | ON HORIZONTAL WOOD FRAMING 2" STAPLES OR |
| | NAILS SHALL BE USED @ EVERY RIB. |
| | |
| | 14) SHEET A-1 LOWER LEFT OF PAGE NOTE |
| | " TYPE III / UNPROTECTED" CORRECT. |
| | |
| | 15)BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH CO.,THE PERMIT PLANS STAMPED BY |
| | THEM AND THE RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. |
| | |
| | 16)PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | ANY QUESTIONS PLEASE CALL, |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | DEPARTMENT OF CONSTRUCTION SERVICES |
| | CITY OF WEST PALM BEACH |
| | (561) 659-8096 EXT. 8412 |