| Plan Review Notes For Permit 02041950 |
| Permit Number |
02041950 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-26 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 02041950 | | | ADD: 3476 COMMODORE CT | | | CONT: HOME DYNAMICS | | | TEL: (954)520-1698 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | REVISION: ACCORDION SHUTTERS | | | ACTION: DENIED | | | | | | 1) PROVIDE STORM PANEL INFORMATION WITH | | | INSTALLATION SCHEDULE AND KEY PLAN WITH | | | SPECIFIC ANCHORS AND MOUNTING TO BE USED | | | FOR ALL NON-IMPACT GLAZING. | | | FBC 1606.1.4. | | | | | | 2)FL BLD CODE 2001 SECTION 103.6, | | | 1606.1.4, 1707.4 & 3401.7.2.4. | | | PROCEDURES: 1(B) A COMPLETE INSTALLATION | | | SCHEDULE SUMMARIZING & IDENTIFYING | | | OPENING SIZES, STORY HEIGHTS, UNIT MARK | | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM | | | BAR REINFORCING REQUIREMENTS, WALL PRES- | | | SURE ZONES, SLAT TYPES, ETC., SHALL BE | | | SUBMITTED AT TIME OF PERMIT APPLICATION | | | TO FACILITATE PLAN REVIEW AND PERMIT | | | ISSUANCE. | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|