| Plan Review Notes For Permit 02041940 |
| Permit Number |
02041940 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHT A-1 MINIMUM FACILITIES REQUIRE A | | | SERVICE SINK. TABLE 403.1 | | | 2) SHT P-2 WATER ISOMETRIC, WATER HAMMER | | | ARRESTORS SHALL BE LOCATED NEAR THE FIX- | | | TURE IN AN "EFFECT RANGE" NOT AT TOP OF | | | DROP AS SHOWN. | | | 3) SHT P-2 INSTANT HOT WATER HEATER, | | | PLEASE SUBMIT MANUFACTURE INFORMATION | | | SHOWING PRODUCT IS LISTED BY APPROVED | | | TESTING AGENCY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|