Plan Review Notes For Permit 02041940
Permit Number 02041940
Review Stop P
Sequence Number 1
Notes
Date Text
2002-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-1 MINIMUM FACILITIES REQUIRE A
 SERVICE SINK. TABLE 403.1
 2) SHT P-2 WATER ISOMETRIC, WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECT RANGE" NOT AT TOP OF
 DROP AS SHOWN.
 3) SHT P-2 INSTANT HOT WATER HEATER,
 PLEASE SUBMIT MANUFACTURE INFORMATION
 SHOWING PRODUCT IS LISTED BY APPROVED
 TESTING AGENCY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377