| Plan Review Notes For Permit 02041940 |
| Permit Number |
02041940 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-21 00:00:00 | ************UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS NEED TO BE SHOWN AT 125%. | | | 215-2/-3,230-42 | | | | | | 2)NOTE: PLEASE NOTE AIC RATING IS SHOWN | | | FOR PANEL BUT NEEDS TO SHOW MAIN DISC. | | | 110-9 | | | | | | 3)NOTE: PLEASE NOTE PLANS NEED TO HAVE | | | "CITY PLACE" STAMP ON THEM. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|