2002-05-21 00:00:00************UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%.
 215-2/-3,230-42
  
 2)NOTE: PLEASE NOTE AIC RATING IS SHOWN
 FOR PANEL BUT NEEDS TO SHOW MAIN DISC.
 110-9
  
 3)NOTE: PLEASE NOTE PLANS NEED TO HAVE
 "CITY PLACE" STAMP ON THEM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  