| Plan Review Notes For Permit 02041882 |
| Permit Number |
02041882 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-16 00:00:00 | 1) PERMIT APPLICATION INDICATES A | | | VALUE OF 1,200.00 DOLLARS. PLEASE | | | PROVIDE A COPY OF CONTRACT OR ADJUST | | | PERMIT VALUE TO CORRECT AMOUNT. | | | | | | 2) PLEASE INDICATE ON THE PLANS THAT | | | SMOKE DETECTORS ARE TO BE INSTALLED A | | | MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | | | | 3) NO ALARMS SHOWN IS MEETING ROOMS | | | 200 B AND 200C. IT APPEARS THESE ROOMS | | | CAN BE SEPARATED FROM THE MAIN TRAINING | | | ROOMS. | | | | | | 4) ARE ALL FLOW AND TAMPER SWITCHES | | | SHOWN ON THE PLANS. | | | | | | 5) FIRE ALARM NOTES # 16 INDICATES | | | SECURITY DEVICES ON DOORS WILL BE TIED | | | INTO THE FIRE ALARM SYSTEM. ALL LOCKING | | | DEVICES ARE MEET THE REQUIREMENTS OF | | | EITHER DELAYED EGRESS OR ACCESS | | | CONTROLLED EGRESS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|