| Plan Review Notes For Permit 02041775 |
| Permit Number |
02041775 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-16 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE PLANS STILL REFER. | | | 96 NECNEEDS 99 NEC. | | | | | | 2)NOTE: PLEASE SHOW ARC PROTECTION PER | | | 210-12 PLEASE LIST. | | | | | | 3 )NOTE: PLEASE CLARIFY EQUIPMENT | | | GROUNDING METHOD BETWEEN FIRST MEANS | | | OF DISCONNECT AND PANELS. PLEASE SIZE | | | CONDUCTORS PER 250-122. | | | | | | 4)NOTE: PLEASE NOTE MISPRINT ON AIC | | | RATING. SHOWN AS 22.00? | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|