| Plan Review Notes For Permit 02041770 |
| Permit Number |
02041770 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-06-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | | | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | | FORMATION REQUIRED FOR PLAN REVIEW | | | 1) FROM PREVIOUS REVIEW - ENGINEERS RE- | | | PORT ON CALCULATIONS FOR 1" VENT ARE FOR | | | A 1HP PUMP, A 2HP PUMP IS BEING USED. | | | SUBMIT CALCUALTIONS FOR A 2" PUMP OR USE | | | 1-1/2" VENT LINES. | | | 2) FBC-2001 424.2.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | | SHEETS REQUIRED. (SUBMITTAL)FROM PREV- | | | IOUS REVIEW. | | | 3) FBC-2001 424.2.14.2 WATER RETENTION, | | | PROVIDE A POSITIVE MEANS OF RETAINING | | | WATER IN THE HEATER WHEN PUMP IS SHUT | | | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) | | | FROM PREVIOUS REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|