| 2002-05-07 00:00:00 | ***************UNSAT *************** |
| | |
| | 1)NOTE; PLEASE NOTE THAT SECOND SERVICE |
| | IS NOT PERMITTED UNLESS ALL IS MET UNDER |
| | 230-2. 2HR SEPARATION FOR ADDITIONAL |
| | SERVICE MAYBE REQ`D FROM OTHER TENANTS. |
| | 2)NOTE: PLEASE NOTE GROUPING OF MAINS |
| | PER 230-72, IF ALL THE REQ`MENTS FOR |
| | 230-2 CAN BE MET. |
| | |
| | 3)NOTE: PLEASE NOTE THAT PANEL SCHEDULE |
| | FOR PANEL "S" WAS SUBMITTED WHICH APPEAR |
| | S TO HAVE NOTHING TO DO WITH THIS TENAT |
| | SPACE? OR DOES IT? PLEASE ALSO NOTE THAT |
| | PANEL "S" IS SHOWING A NEW AHU (MS-1)?? |
| | PLEASE CALRIFY WHERE THIS IS SHOWN? AND |
| | WIRING FOR UNIT ON RISER. |
| | |
| | 4)NOTE: PLEASE ALSO NOTE THAT PANEL |
| | SCHEDULE FOR PANEL "N" IS SHOWING TWO |
| | NEW COND UNITS??? PLANS/RISER ONLY SHOW |
| | ONE NEW CU #1? PLEASE CLARIFY. |
| | |
| | 5)NOTE: PLEASE NOTE PANEL SCHEDULE FOR |
| | PANEL "N" HAS A FEED (2P 80) FOR "T2"?? |
| | PLEASE CLARIFY. |
| | |
| | 6)NOTE: PLEASE NOTE THAT PANEL MR1 IS |
| | NOT SHOWN ON PANEL SCHEDULE "N"? |
| | PLEASE CLARIFY. |
| | |
| | 7)NOTE: PLEASE NOTE/CLARIFY ADDITIONAL |
| | AHU SHOWN AS 1POLE 20A?? ON PANEL "N"?? |
| | |
| | 8)NOTE: PLEASE CLARIFY NEW OR EXISTING |
| | RECEPT FOR ROOFTOP A/C EQUIPMENT? 210-63 |
| | |
| | 9 )NOTE: PLEASE NOTE THAT THE LOAD |
| | CALCULATIONS NEED TO BE SHOWN. SQ FT/ |
| | RECEPT LOADS ETC. PER 220-3,220-10, |
| | 220-11, 220-13. (215-5) |
| | |
| | 10)NOTE: PLEASE SHOW ALL CONTINUOUS AT |
| | 125%. (LIGHTING ETC) |
| | 215-2,215-3,230-42 |
| | |
| | 11)NOTE: PLEASE NOTE NO WIRE SIZES ARE |
| | SHOWN ON PANEL SCHEDULES?? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |