Plan Review Notes
Plan Review Notes For Permit 02041743
Permit Number 02041743
Review Stop E
Sequence Number 3
Notes
Date Text
2002-11-19 00:00:00************** UNSAT *****************
  
 PLEASE NOTE THAT DUE TO THE FACT THAT
 PLANS ARE IN FOR FINAL REVIEWAND
 FOR FINAL INPSECTION, THE FOLLOWING ITEM
 -S NNED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SHOW AIC RATINGS FOR
 NEW EQUIPMENT/MAINS/BRKRS. 110-9/215-5
  
 2)NOTE: PLEASE NOTE, OCP FOR 10KW AHU
 NEEDS TO BE SIZED TO A MIN 125%. PER
 424-3
  
 3)NOTE: PLEASE NOTE, MISSING REQ`D ARC
 FAULT PROTECTED CIRCUITS PER 210-12.
 PLEASE LIST ON PANEL SCHEDULE.
  
 4)NOTE: PLEASE NOTE MISSING REQ`D BATH
 CIRCUIT(S) PER 210-11-C3
 #12, 20A.
  
 5)NOTE: PLEASE NOTE, PANEL SCHEDULE
 SHOWS 4 CIRCUITS FOR SMALL APPLIANCES
 AND ONLY 3 ON LOAD CALCS?
 PLEASE CORRELATE.
  
 6)NOTE: PLEASE NOTE, PANEL "A" HAS SUB
 FEED. PLEASE ALSO NOTE,
 THERE IS NOTHING SHOWN ON PANEL "A'
 FOR SUB-FEED OF PANEL "B". BRKR SIZE,
 WIRE SIZE, CONDUIT, LOCATION ETC.
  
 7)NOTE: PLEASE NOTE, SD IN BEDROOM #3
 IS TO BE A MIN OF 3' FROM BATHS.
 NFPA-72 8-1.4.1.6
  
 PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372