| Plan Review Notes For Permit 02041743 |
| Permit Number |
02041743 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-11-19 00:00:00 | ************** UNSAT ***************** | | | | | | PLEASE NOTE THAT DUE TO THE FACT THAT | | | PLANS ARE IN FOR FINAL REVIEWAND | | | FOR FINAL INPSECTION, THE FOLLOWING ITEM | | | -S NNED TO BE ADDRESSED. | | | | | | 1)NOTE: PLEASE SHOW AIC RATINGS FOR | | | NEW EQUIPMENT/MAINS/BRKRS. 110-9/215-5 | | | | | | 2)NOTE: PLEASE NOTE, OCP FOR 10KW AHU | | | NEEDS TO BE SIZED TO A MIN 125%. PER | | | 424-3 | | | | | | 3)NOTE: PLEASE NOTE, MISSING REQ`D ARC | | | FAULT PROTECTED CIRCUITS PER 210-12. | | | PLEASE LIST ON PANEL SCHEDULE. | | | | | | 4)NOTE: PLEASE NOTE MISSING REQ`D BATH | | | CIRCUIT(S) PER 210-11-C3 | | | #12, 20A. | | | | | | 5)NOTE: PLEASE NOTE, PANEL SCHEDULE | | | SHOWS 4 CIRCUITS FOR SMALL APPLIANCES | | | AND ONLY 3 ON LOAD CALCS? | | | PLEASE CORRELATE. | | | | | | 6)NOTE: PLEASE NOTE, PANEL "A" HAS SUB | | | FEED. PLEASE ALSO NOTE, | | | THERE IS NOTHING SHOWN ON PANEL "A' | | | FOR SUB-FEED OF PANEL "B". BRKR SIZE, | | | WIRE SIZE, CONDUIT, LOCATION ETC. | | | | | | 7)NOTE: PLEASE NOTE, SD IN BEDROOM #3 | | | IS TO BE A MIN OF 3' FROM BATHS. | | | NFPA-72 8-1.4.1.6 | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|