Plan Review Notes
Plan Review Notes For Permit 02041743
Permit Number 02041743
Review Stop M
Sequence Number 2
Notes
Date Text
2002-06-20 00:00:00PROVISO:
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 DRYER INSTALLATIONS EXHASUTING MORE THAN
 200 CFM SHALL BE PROVIDED WITH MAKEUP
 AIR AS PER 2001 FBC(M) 504.5
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.