| Plan Review Notes For Permit 02041743 |
| Permit Number |
02041743 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-21 00:00:00 | UNSAT! | | | ~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} CONTACT FPL REGARDING THE 2"METAL | | | CONDUIT SHOWN ON THE RISER DIAGRAM, | | | THEY NORMALLY SUPPLY PVC. | | | | | | 3} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12 | | | | | | 4} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 5} THERE IS NO CALCULATION INCLUDED OR | | | LISTING ON THE PANEL SCHEDULE FOR THE | | | STEAM GENERATOR,PLEASE CLARIFY. | | | | | | 6} PLEASE COMPLY WITH NFPA-72 2-2.1.1.1 | | | DROOM #3 | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|