Plan Review Notes
Plan Review Notes For Permit 02041743
Permit Number 02041743
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-21 00:00:00UNSAT!
 ~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} CONTACT FPL REGARDING THE 2"METAL
 CONDUIT SHOWN ON THE RISER DIAGRAM,
 THEY NORMALLY SUPPLY PVC.
  
 3} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 4} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} THERE IS NO CALCULATION INCLUDED OR
 LISTING ON THE PANEL SCHEDULE FOR THE
 STEAM GENERATOR,PLEASE CLARIFY.
  
 6} PLEASE COMPLY WITH NFPA-72 2-2.1.1.1
 DROOM #3
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392