| 2002-06-04 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT:02041740 |
| | ADD: 9574 LANTERN BAY CIR |
| | CONT: ENGLE HOMES |
| | TEL: 968-5671 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | *******BUILDING- FAILED********* |
| | FL BLDG 1909.3 (EXEPTION# 2) |
| | CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| | PORTED BY APPROVED MATERIALS OR SUPPORTS |
| | AT SPACING NOT TO EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURER'S SPEC. |
| | CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| | PORTED BY APPROVED MATERIALS OR SUPPORTS |
| | AT SPACING NOT TO EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURER'S SPEC. |
| | |
| | 2) PROVIDE PRODUCT TESTING REPORT FOR |
| | THE ROOFING ASSEMBLY BEFORE ROOF FRAMING |
| | INSPECTION. |
| | |
| | 3) THE DESIGN PARAMETERS & ASSUMPTIONS |
| | ARE DESIGNED TO THE 1997 STANDARD BUILD- |
| | ING CODE NOT THE 2001 FLORIDA BUIULDING |
| | CODE. |
| | |
| | ANY QUESTIONS PLEASE CALL, |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |