Plan Review Notes
Plan Review Notes For Permit 02041710
Permit Number 02041710
Review Stop R
Sequence Number 1
Notes
Date Text
2002-06-10 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED.
  
 3) THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
 PLEASE UPDATE THE DESIGN ASSUMPTIONS AND
 PARAMETERS ON S1.
  
 4) PLEASE INDICATE THE POSITIVE AND
 NEGATIVE WINDLOAD PRESSURES FOR THE
 SKYLIGHT AND THE 25 SH WINDOW IN THE
 GARAGE.
  
 5) PLEASE REVISE NOTE #2 ON A1 TO THE
 FLORIDA BUILDING CODE.
  
 6) PLEASE REVISE THE BUCK DETAIL #2 ON
 A4 TO COMPLY WITH FBC 1707.4.4.2.
  
 7) PLEASE UPDATE THE FOLLOWING NOTES ON
 S4 TO REFERENCE THE 2001 FBC:
 - #3 & #4 UNDER GENERAL NOTES
 - #9 UNDER GENERAL NOTES TO ASCE 7-98 &
 140MPH (3 SEC. GUST)
 - #1 UNDER SAFEGUARDS
 - #1 UNDER REINFORCED CONCRETE
 - #2 UNDER TRUSSES
 - #5 UNDER ROOF SHEATHING
  
 8) PLEASE REVISE NOTE #7, THE CORRECT
 REFERENCE IS ASTM A 185. THE WELDED WIRE
 FABRIC IS REQUIRED TO BE SUPPORTED WITH
 APPROVED MATERIALS OR SUPPORTS PER FBC
 SEC. 1909.3.
  
 9) THE NEGATIVE PRESSURE FOR THE 1/2-36
 SINGLE HUNG KDI WINDOWS IN THE DEN AND
 THE LIVING ROOM EXCEEDS THE VALUE LISTED
 IN THE SBCCI PRODUCT EVALUATION REPORT.
 THE COMPARATIVE ANALYSIS CHART IS NOT
 VALID WITHOUT THE WET SIGNATURE AND
 EMBOSSED SEAL OF THE ENGINEER.
  
 10) THE KEY PLAN AND INSTALLATION
 SCHEDULE SUBMITTED FOR THE STORM PANELS
 ARE FOR ANOTHER MODEL. PLEASE SUBMIT THE
 ONES FOR A "B" MODEL.
  
 11) THE PRODUCT APPROVAL FOR ENTEGRA
 ROOF TILE IS EXPIRED.
  
 12) PROVIDE PRODUCT APPROVALS FOR AN
 EXTERIOR DOOR WITH SIDELITE AS SHOWN ON
 PLANS.
  
 13) PROVIDE THE CORRECT GARAGE DOOR
 DRAWING THE ONE ATTACHED TO THE PRODUCT
 APPROVAL IS FOR A 9 FOOT WIDE DOOR
 MAXIMUM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202