Plan Review Notes
Plan Review Notes For Permit 02041683
Permit Number 02041683
Review Stop E
Sequence Number 3
Notes
Date Text
2002-07-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING DICREPANCIES,
 CORRECT PLANS AND RESUBMIT FOR REVIEW:
  
 1} INCLUDE SMALL APPLIANCE CIRCUITS IN
 LOAD CALCULATIONS PER 220-30.
  
 2} SHOW KITCHEN CIRCUITS ON PANEL
 SCHEDULE.(APPLIANCE).
  
 3} CIRCUIT #18 IS LABELED "KITCHEN BATH
 RECEPT".PLEASE CLARIFY.
  
 4} THE MICROWAVE IN THE CALCULATIONS IS
 NOT LISTED ON THE PANEL SCHEDULE.
  
 5} PLEASE REMOVE THE SMOKE DETECTOR FROM
 THE BATHROOM PER NFPA-72 2-5.2.1.6.
  
 6} THE RANGE LISTED AT 5000W MUST COMPLY
 WITH 220-19.
  
 7} PLEASE REMOVE THE #4 GROUND FROM THE
 METER TO THE PANEL AS IT CREATES A
 PARALLEL PATH WITH THE
 GROUNDED(NEUTRAL) CONDUCTOR.
  
 8} PLEASE NOTE THAT ITEMS #1&2 WERE
 NOTED ON THE PREVIOUS TWO REVIEWS AND
 ARE SUBJECT TO FLORIDA STATUTE
 553.80(2)(B),SHOULD THEY NOT BE
 CORRECTED.SEE ATTACHED COPY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL:
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392