| Plan Review Notes For Permit 02041683 |
| Permit Number |
02041683 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-07-18 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THE FOLLOWING DICREPANCIES, | | | CORRECT PLANS AND RESUBMIT FOR REVIEW: | | | | | | 1} INCLUDE SMALL APPLIANCE CIRCUITS IN | | | LOAD CALCULATIONS PER 220-30. | | | | | | 2} SHOW KITCHEN CIRCUITS ON PANEL | | | SCHEDULE.(APPLIANCE). | | | | | | 3} CIRCUIT #18 IS LABELED "KITCHEN BATH | | | RECEPT".PLEASE CLARIFY. | | | | | | 4} THE MICROWAVE IN THE CALCULATIONS IS | | | NOT LISTED ON THE PANEL SCHEDULE. | | | | | | 5} PLEASE REMOVE THE SMOKE DETECTOR FROM | | | THE BATHROOM PER NFPA-72 2-5.2.1.6. | | | | | | 6} THE RANGE LISTED AT 5000W MUST COMPLY | | | WITH 220-19. | | | | | | 7} PLEASE REMOVE THE #4 GROUND FROM THE | | | METER TO THE PANEL AS IT CREATES A | | | PARALLEL PATH WITH THE | | | GROUNDED(NEUTRAL) CONDUCTOR. | | | | | | 8} PLEASE NOTE THAT ITEMS #1&2 WERE | | | NOTED ON THE PREVIOUS TWO REVIEWS AND | | | ARE SUBJECT TO FLORIDA STATUTE | | | 553.80(2)(B),SHOULD THEY NOT BE | | | CORRECTED.SEE ATTACHED COPY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL: | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|