Plan Review Notes
Plan Review Notes For Permit 02041683
Permit Number 02041683
Review Stop E
Sequence Number 2
Notes
Date Text
2002-07-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE NOTE THE FOLLOWING
 DISCREPANCIES,CORRECT PLANS AND
 RESUBMIT FOR REVIEW:
  
 1} INCLUDE SMALL APPLIANCE CIRCUITS IN
 LOAD CLCULATIONS PER 220-30.
  
 2} SHOW KITCHEN CIRCUITS ON PANEL
 SCHEDULE.(APPLIANCE).
  
 3} A/C #1 AHU @ 10K,BREAKER & BRANCH
 CIRCUIT CONDUCTORS ARE UNDERSIZED PER
 424-3(B).
  
 4} THE RANGE LISTED AT 5000W MUST COMPLY
 WITH 220-19.
  
 PLEASE NOTE THAT ITEMS #1,2 & 3 WERE
 NOTED ON THE PREVIOUS REVIEW NOTES.IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392