Plan Review Notes
Plan Review Notes For Permit 02041683
Permit Number 02041683
Review Stop R
Sequence Number 1
Notes
Date Text
2002-06-03 00:00:00BUILDING DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES FOR THE SKYLIGHT ON THE PLANS.
  
 3) PLEASE REVIEW THE M.O. LISTED FOR THE
 1/2 33SH WINDOW, IT APPEARS TO BE TOO
 LARGE.
  
 4) PLEASE REVIEW THE POSITIVE AND
 NEGATIVE PRESSURES THAT ARE GIVEN FOR
 THE WINDOW AND DOOR OPENINGS, SOME OF
 THEM APPEAR TO BE TOO HIGH.
  
 5) INDICATE COMPLIANCE WITH TABLE 600
 (PERCENTAGE OF WALL AREA ALLOWED AS
 OPENINGS) FOR THE MASTER BEDROOM WALL
 WITH SLIDING GLASS DOOR AND AND THE
 LIVING ROOM WALL WITH THE SLIDING GLASS
 DOOR. ALSO REVIEW THE AREAS OF THE
 OPENINGS USED IN THE CALCULATIONS ON
 SHEET A2.
  
 6) INDICATE ON THE PLANS THAT THE WELDED
 WIRE REINFORCEMENT FABRIC WILL BE
 SUPPORTED WITH APPROVED MATERIALS OR
 SUPPORTS PER 2001 FBC SEC. 1909.3.
  
 7) REVISE ITEM #2 ON A1 TO REFERENCE THE
 FLORIDA BUILDING CODE.
  
 8) PLEASE REVISE DETAIL 2 ON A4 TO SHOW
 BUCKS EXTENDING BEYOND THE FACE OF THE
 WINDOW/ DOOR FRAMES TO PROVIDE FULL
 SUPPORT AND THE FRAME ANCHORS EXTENDING
 THROUGH THE 1X BUCKS INTO THE STRUCTURAL
 SUBSTRATE MATERIAL AS REQUIRED BY 2001
 FBC SECTION 1707.4.4.2.
  
 9) PLEASE UPDATE THE STRUCTURAL DESIGN
 PARAMETERS AND ASSUMPTIONS ON S1 TO
 REFLECT THE 2001 FBC AND ASCE 7-98.
 THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 10) PLEASE UPDATE THE NOTES ON S4 IN
 SEVERAL PLACES TO REFERENCE THE 2001
 FLORIDA BUILDING CODE AND ASCE 7-98.
  
 11) PLEASE SUBMIT THE CURRENT SBCCI
 EVALUATION REPORT FOR THE KDI DOORS AND
 WINDOWS. REPORT # 9733A.
  
 12) PROVIDE AN ORIGINAL SIGNED, SEALED
 AND DATED ANALYSIS CHART WITH THE
 ENGINEER'S CALCULATIONS FOR THE KDI
 SINGLE HUNG WINDOWS.
  
 13) THE PRODUCT APPROVAL FOR THE ENTEGRA
 ROOF TILE EXPIRED ON 10-01-01. PLEASE
 SUBMIT CURRENT PRODUCT APPROVALS.
  
 14) PLEASE REVIEW THE OPENING SIZES ON
 STORM PANEL INSTALLATION SCHEDULE AND
 CORRECT AS NECESSARY. (BATHROOM WINDOW)
  
 NOTE: TRUSS DRAWINGS AND LAYOUT ARE NO
 LONGER REQUIRED TO BE SUBMITTED FOR
 PLAN REVIEW. A SIGNED,SEALED AND DATED
 SET OF DRAWINGS AND LAYOUT WILL BE
 REQUIRED FOR REVIEW IN THE FIELD BY THE
 BUILDING INSPECTOR AT TIME OF TRUSS
 INSPECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202