Plan Review Notes
Plan Review Notes For Permit 02041683
Permit Number 02041683
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-15 00:00:00~~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~
  
 PLEASE NOTE THE FOLLOWING
 DISCREPANCIES,CORRECT PLANS AND
 RESUBMIT FOR REVIEW.
  
 1} INCLUDE SMALL APPLIANCE CIRCUITS IN
 LOAD CALCULATIONS PER 220-30.
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 3} SHOW KITCHEN CIRCUITS ON PANEL
 SCHEDULE.(APPLIANCE).
  
 4} A/C #1 AHU @ 10K,BREAKER & BRANCH
 CIRCUIT CONDUCTORS ARE UNDERSIZED
 PER424-3(B). 65% FOR CALCULATIONS
 ONLY,NOT B.C.& OCP.
  
 5} THE WASHER IS LISTED AT 3000W IN THE
 LOAD CALCS AND SHOWN ON A 20 AMP
 BREAKER WITH #12 WIRE ON THE PANEL
 SCHEDULE, PLEASE CLARIFY.
  
 6} OVEN SHOWN ON PANEL SCHEDULE BUT NOT
 IN LOAD CALCULATION,PLEASE CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392