| Plan Review Notes For Permit 02041671 |
| Permit Number |
02041671 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-14 00:00:00 | 1) PLANS DO NOT INDICATE LOCATIONS OF | | | FIRE HYDRANT LOCATIONS. | | | | | | 2) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO,DURING AND AFTER CONSTRUCTION. | | | | | | 3) ELECTRIC POWERED SMOKE DETECTORS ARE | | | REQUIRED. | | | | | | 4) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | | | | 5) PLEASE CLEARLY INDICATE LOCATIONS | | | OF ALL EGRESS WINDOWS. | | | | | | 6) TENANT SEPARATIONS ARE TO COMPLY | | | WITH APPLICABLE CODES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|