| Plan Review Notes For Permit 02041656 |
| Permit Number |
02041656 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-15 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT THE OVEN THAT | | | IS SHOWN ON PANEL SCHEDULE IS NOT SHOWN | | | ON LOAD CALCUALTIONS. PLEASE CORRELATE. | | | | | | 2)NOTE: PLEASE NOTE A 10KW LOAD SHOWN | | | W/ 50A OCP AND #8 AWG. PLEASE SEE 424-3B | | | | | | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTION PER 210-12 ON PANEL SCHEDULE. | | | | | | 4)NOTE: PLEASE CLARIFY, PLANS SAYS | | | MAIN DISC NEXT TO METER AND PLANS SHOW | | | NEXT TO PANEL INSIDE GARAGE? PLEASE | | | CORRELATE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | 5)NOTE: PLEASE NOTE THAT GROUNDING | | | ELECTRODE CONDUCTOR SIZED PER 250-66 | | | 3/0`S....... |
|