| Plan Review Notes For Permit 02041653 |
| Permit Number |
02041653 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FHA AMEND-98 DESIGN MANUAL | | | | | | 1) SHT A3.01 UNITS A/A-REV, INDICATE | | | SPECIFICATION A OR B REQUIREMENT 7. | | | 2) SHT A3.02 UNITS B/B-REV, INDICATE | | | SPECIFICATION A OR B REQUIREMENT 7. | | | SHOW CLEAR FLOOR SPACE FOR ALL REQUIRED | | | FIXTURES. | | | 3) SHT A3.03 UNITS C/C-REV INDICATE | | | SPECIFICATION A OR B REQUIREMENT 7. | | | SHT P-101, BLDG 1 PLUMBING LAYOUT PLAN, | | | OUTSIDE UNITS SECTION 504.7.1 THE DIS- | | | CHARGE PIPE FROM THE RELIEF VALVE FROM | | | THE WATER HEATER SHALL HAVE NOT TRAPPED | | | SECTIONS AND SHALL HAVE A VISIBLE AIR | | | GAP OR AIR GAP FITTING LOCATED IN THE | | | SAME ROOM AS THE WATER HEATER. | | | 4) SHT P-105 WATER RISERS, WATER HAMMER | | | ARRESTORS ARE REQUIRED AT THE WASH MACH- | | | INE. 604.9 | | | 5) SHT P-106 BACKFLOW /WATER HEATER DE- | | | TAILS. IF A BACKFLOW IS INSTALLED ON THE | | | WATER SERVICE, THERMAL EXPANSION CONTROL | | | SHALL BE REQUIRED. 607.3 - 607.3.2. | | | 6) COND. SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|