Plan Review Notes
Plan Review Notes For Permit 02041653
Permit Number 02041653
Review Stop P
Sequence Number 1
Notes
Date Text
2002-05-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 1) SHT A3.01 UNITS A/A-REV, INDICATE
 SPECIFICATION A OR B REQUIREMENT 7.
 2) SHT A3.02 UNITS B/B-REV, INDICATE
 SPECIFICATION A OR B REQUIREMENT 7.
 SHOW CLEAR FLOOR SPACE FOR ALL REQUIRED
 FIXTURES.
 3) SHT A3.03 UNITS C/C-REV INDICATE
 SPECIFICATION A OR B REQUIREMENT 7.
 SHT P-101, BLDG 1 PLUMBING LAYOUT PLAN,
 OUTSIDE UNITS SECTION 504.7.1 THE DIS-
 CHARGE PIPE FROM THE RELIEF VALVE FROM
 THE WATER HEATER SHALL HAVE NOT TRAPPED
 SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING LOCATED IN THE
 SAME ROOM AS THE WATER HEATER.
 4) SHT P-105 WATER RISERS, WATER HAMMER
 ARRESTORS ARE REQUIRED AT THE WASH MACH-
 INE. 604.9
 5) SHT P-106 BACKFLOW /WATER HEATER DE-
 TAILS. IF A BACKFLOW IS INSTALLED ON THE
 WATER SERVICE, THERMAL EXPANSION CONTROL
 SHALL BE REQUIRED. 607.3 - 607.3.2.
 6) COND. SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377