| 2002-05-30 00:00:00 | MASTER PERMIT 02041653 |
| | |
| | 2001 FBC(M) 402.2 - NATURAL VENTILATION |
| | FOR OUTSIDE AIR REQUIRMENT. SHOW |
| | COMPLIANCE FOR THE MINIMUM OPENABLE AREA |
| | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR |
| | AREA BEING VENTILATED) OR TABLE 403.3 |
| | FOR MECHANICAL VENTILATION. |
| | |
| | BALANCED RETURN AIR - 2001 FBC(M) 601.4 |
| | PRESSURE DIFFERNTIALS ACROSS CLOSED |
| | DOORS WHERE RETURNS ARE CENTRALLY |
| | LOCATED SHALL BE LIMITED TO .001" WC OR |
| | LESS. PROVIDE AIR DUCT PATHWAYS OR AIR |
| | TRANSFER PATHWAYS FROM THE HIGH PRESSURE |
| | ZONE TO THE LOW ZONE. |
| | |
| | CONDENSATE SHALL DISCHARGE A MINIMUM OF |
| | 12" AWAY FROM THE BUILDING STRUCTURE AS |
| | PER 2001 FBC 1503.4.4. PLAN SHEET P-101 |
| | INDICATES OVERFLOW TERMINATING OUTSIDE. |
| | CODE DICTATES "CONSPICUOUS POINT TO |
| | SERVE AS ALARM WHICH INDICATES THAT THE |
| | PRIMARY DRAIN IS RESTRICTED".CLARIFY |
| | HOW HOME OWNER WILL KNOW PRIMARY DRAIN |
| | IS RESTRICTED WHEN THE TERMINATION POINT |
| | IS OUTSIDE NEXT TO THE PRIMARY DRAIN. |
| | |
| | PLAN SHEET M-105 - AHU MOUNTING DETAIL, |
| | DETAIL INDICATES 3" BETWEEN DUCT AND |
| | DRYWALL.AS PER 2001 FBC(M) 603.1.3, |
| | SPACE PROVIDED - TO ASSURE ADEQUATE |
| | ACCESS FOR (1) CONSTRUCTION & SEALING |
| | IN ACCORDANCE WITH THE REQUIREMENTS OF |
| | SECTION 603.1 FBC(M) (2) INSPECTION.A |
| | MINIMUM OF 4" IS CONSIDERED SUFFICIENT |
| | SPACE. |
| | |
| | PLANS M-102, 103 & 104, NOTE FOR DRYER |
| | EXHAUST INDICATES 4" UP THRU ROOF W/WP |
| | CAP, INSECT SCREEN & B.D.D.DRYER EXHAUST |
| | IS TO BE "NON-SCREENED" WITH B.D.D. |
| | PLEASE ALSO CORRECT WORDING ON PLAN M105 |
| | |
| | SHOW COMPLIANCE TO THE 2001 FBC(M) 303.4 |
| | & 304.4, PROTECTION FOR EQUIPMENT IN |
| | PRIVATE GARAGE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |