Plan Review Notes
Plan Review Notes For Permit 02041653
Permit Number 02041653
Review Stop B
Sequence Number 1
Notes
Date Text
2002-05-29 00:00:00PLAN REVIEW, (NOT A PERMIT
 APPLICATION),FOR LIGHTHOUSE POINT AT
 BAYWINDS.THE PLANS PROPOSE A SERIES
 OF TOWNHOUSES IN 6 AND 4 UNIT CLUSTERS.
  
 EACH TOWNHOUSE UNIT WILL REQUIRE A
 SEPARATE PERMIT.
  
 THE SBCCI REPORT #9755 FOR THE AMARR
 GARAGE DOORS IS EXPIRED.
  
 THE FOLLOWING MIAMI DADE REPORTS ARE
 EXPIRED:
  
 PCA 98-1228.01PCA 95-1212.01
 PCA 99-1203.02
  
 SHEET T1.00 GENERAL NOTES 1 AND 5 ARE
 NOT IN AGREEMENT.ONE DECLARES
 "TOWNHOUSES" (R3) AND 5 CALLS OUT "R2"
 PLEASE REVISE AS NECESSARY.SEE FBC 311
 AND FBC 704.4.
  
 ALSO THE CONSTRUCTION TYPE IS NOTED
 AS"II" TYPE VI IS IN AGREEMENT WITH THE
 PLANS. PLEASE REVISE AS NECESSARY.
  
 SHEET SP 1.01 HAS THE WRONG DIMENSIONS
 ON THEM.PLEASE CLARIFY.
  
 THE PLANS HAVE VARIOUS REFERENCES TO THE
 FORMER SOUTH FLORIDA BUILDING CODE.
 PLEASE REVISE AND ENSURE COMPLIANCE
 WITH THE FLORIDA BUILDING CODE, 2001.
  
 SHEET A3.03 SHOWS VENTS IN THE GARAGE
 DOOR.THESE MUST BE COVERED IN THE
 PRODUCT TEST REPORTS AND ACCEPTANCE
 NOTICE.
  
 SHEET 4/A6.01 SHOWS THE FRT SHEATHING
 MEASURED FOUR FEET FROM THE PARTY WALL
 CENTER LINE. FBC REQUIRES THE
 PROTECTION TOBE FOUR FEET TO EACH SIDE
 OF THE WALL, REVISE AS NECESSARY.SEE
 FBC 704.4.
  
 SHOW THE WIND PRESSURE ZONES FOR THE
 ROOF.
  
 SECTION 2 A/601 SHOWS A STEP AT THE
 FRONT ENTRANCE PORCH WHICH IS IN
 CONFLICT FOR AN ACCESSIBLE ENTRANCE
 WITH THE FAIR HOUSING ACT.PLEASE
 REVISE AS NECESSARY.