| 2002-05-29 00:00:00 | PLAN REVIEW, (NOT A PERMIT |
| | APPLICATION),FOR LIGHTHOUSE POINT AT |
| | BAYWINDS.THE PLANS PROPOSE A SERIES |
| | OF TOWNHOUSES IN 6 AND 4 UNIT CLUSTERS. |
| | |
| | EACH TOWNHOUSE UNIT WILL REQUIRE A |
| | SEPARATE PERMIT. |
| | |
| | THE SBCCI REPORT #9755 FOR THE AMARR |
| | GARAGE DOORS IS EXPIRED. |
| | |
| | THE FOLLOWING MIAMI DADE REPORTS ARE |
| | EXPIRED: |
| | |
| | PCA 98-1228.01PCA 95-1212.01 |
| | PCA 99-1203.02 |
| | |
| | SHEET T1.00 GENERAL NOTES 1 AND 5 ARE |
| | NOT IN AGREEMENT.ONE DECLARES |
| | "TOWNHOUSES" (R3) AND 5 CALLS OUT "R2" |
| | PLEASE REVISE AS NECESSARY.SEE FBC 311 |
| | AND FBC 704.4. |
| | |
| | ALSO THE CONSTRUCTION TYPE IS NOTED |
| | AS"II" TYPE VI IS IN AGREEMENT WITH THE |
| | PLANS. PLEASE REVISE AS NECESSARY. |
| | |
| | SHEET SP 1.01 HAS THE WRONG DIMENSIONS |
| | ON THEM.PLEASE CLARIFY. |
| | |
| | THE PLANS HAVE VARIOUS REFERENCES TO THE |
| | FORMER SOUTH FLORIDA BUILDING CODE. |
| | PLEASE REVISE AND ENSURE COMPLIANCE |
| | WITH THE FLORIDA BUILDING CODE, 2001. |
| | |
| | SHEET A3.03 SHOWS VENTS IN THE GARAGE |
| | DOOR.THESE MUST BE COVERED IN THE |
| | PRODUCT TEST REPORTS AND ACCEPTANCE |
| | NOTICE. |
| | |
| | SHEET 4/A6.01 SHOWS THE FRT SHEATHING |
| | MEASURED FOUR FEET FROM THE PARTY WALL |
| | CENTER LINE. FBC REQUIRES THE |
| | PROTECTION TOBE FOUR FEET TO EACH SIDE |
| | OF THE WALL, REVISE AS NECESSARY.SEE |
| | FBC 704.4. |
| | |
| | SHOW THE WIND PRESSURE ZONES FOR THE |
| | ROOF. |
| | |
| | SECTION 2 A/601 SHOWS A STEP AT THE |
| | FRONT ENTRANCE PORCH WHICH IS IN |
| | CONFLICT FOR AN ACCESSIBLE ENTRANCE |
| | WITH THE FAIR HOUSING ACT.PLEASE |
| | REVISE AS NECESSARY. |