Plan Review Notes
Plan Review Notes For Permit 02041645
Permit Number 02041645
Review Stop P
Sequence Number 1
Notes
Date Text
2002-05-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 1) SHT A3.02 UNITS B/B-REV PLEASE SHOW
 CLEAR FLOOR SPACE FOR ALL FIXTURES.
 2) SHT A3.02 UNITS B/B-REV INDICATE
 SPECIFICATION A OR B REQUIREMENT 7. SEE
 EXAMPLES PAGES 7.36 & 7.37.
 3) SHT A3.03 UNITS C/C-REV INDICATE
 SPECIFICATION A OR B, REQUIREMENT 7
 4) SHT P-201 BLDG 2: PLUMBING LAYOUT
 PLAN, OUTSIDE UNITS. SECTION 504.7.1 THE
 DISCHARGE PIPE FROM THE RELIEF VALVE
 FROM THE WATER HEATER SHALL HAVE NO
 TRAPPED SECTIONS AND SHALL HAVE A VISIB-
 LE AIR GAP OR AIR GAP FITTING LOCATED IN
 THE SAME ROOM AS THE WATER HEATER. SEC.
 504.7.1
 5) SHT P-204 WATER RISERS, WATER HAMMER
 ARRESTORS ARE REQUIRED AT THE WASH MACH-
 INE. SEC 604.9
 6) SHT P-205 DRAIN PAN/RVD DISCHARGE DE-
 TAIL, SEC 504.7.1 NO TRAPPED SECTIONS IN
 RELIEF VALVE DISCHARGE.
 7) SHT P-205 BACKFLOW DETAIL. IF BACK-
 FLOW IS USED, THERMAL EXPANSION CONTROL
 SHALL BE REQUIRED. 607.3 - 607.3.2
 8) CONDENSATE LINES SHALL DISCHARGE AT
 LEAST 1 FOOT AWAY FROM THE STRUCTURE
 SIDEWALL. 1503.4.4 FBC
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377