| 2002-05-20 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FHA AMEND-98 DESIGN MANUAL |
| | |
| | 1) SHT A3.02 UNITS B/B-REV PLEASE SHOW |
| | CLEAR FLOOR SPACE FOR ALL FIXTURES. |
| | 2) SHT A3.02 UNITS B/B-REV INDICATE |
| | SPECIFICATION A OR B REQUIREMENT 7. SEE |
| | EXAMPLES PAGES 7.36 & 7.37. |
| | 3) SHT A3.03 UNITS C/C-REV INDICATE |
| | SPECIFICATION A OR B, REQUIREMENT 7 |
| | 4) SHT P-201 BLDG 2: PLUMBING LAYOUT |
| | PLAN, OUTSIDE UNITS. SECTION 504.7.1 THE |
| | DISCHARGE PIPE FROM THE RELIEF VALVE |
| | FROM THE WATER HEATER SHALL HAVE NO |
| | TRAPPED SECTIONS AND SHALL HAVE A VISIB- |
| | LE AIR GAP OR AIR GAP FITTING LOCATED IN |
| | THE SAME ROOM AS THE WATER HEATER. SEC. |
| | 504.7.1 |
| | 5) SHT P-204 WATER RISERS, WATER HAMMER |
| | ARRESTORS ARE REQUIRED AT THE WASH MACH- |
| | INE. SEC 604.9 |
| | 6) SHT P-205 DRAIN PAN/RVD DISCHARGE DE- |
| | TAIL, SEC 504.7.1 NO TRAPPED SECTIONS IN |
| | RELIEF VALVE DISCHARGE. |
| | 7) SHT P-205 BACKFLOW DETAIL. IF BACK- |
| | FLOW IS USED, THERMAL EXPANSION CONTROL |
| | SHALL BE REQUIRED. 607.3 - 607.3.2 |
| | 8) CONDENSATE LINES SHALL DISCHARGE AT |
| | LEAST 1 FOOT AWAY FROM THE STRUCTURE |
| | SIDEWALL. 1503.4.4 FBC |
| | |
| | REVIEW BY KEN STEVENS |