2002-05-30 00:00:00MASTER PERMIT 02041645
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 PRESSURE DIFFERNTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001" WC OR
 LESS. PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH PRESSURE
 ZONE TO THE LOW ZONE.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.PLAN SHEET P-201
 INDICATES OVERFLOW TERMINATING OUTSIDE.
 CODE DICTATES "CONSPICUOUS POINT TO
 SERVE AS ALARM WHICH INDICATES THAT THE
 PRIMARY DRAIN IS RESTRICTED".CLARIFY
 HOW HOME OWNER WILL KNOW PRIMARY DRAIN
 IS RESTRICTED WHEN THE TERMINATION POINT
 IS OUTSIDE NEXT TO THE PRIMARY DRAIN.
  
 PLAN SHEET M-204 - AHU MOUNTING DETAIL,
 DETAIL INDICATES 3" BETWEEN DUCT AND
 DRYWALL.AS PER 2001 FBC(M) 603.1.3,
 SPACE PROVIDED - TO ASSURE ADEQUATE
 ACCESS FOR (1) CONSTRUCTION & SEALING
 IN ACCORDANCE WITH THE REQUIREMENTS OF
 SECTION 603.1 FBC(M) (2) INSPECTION.A
 MINIMUM OF 4" IS CONSIDERED SUFFICIENT
 SPACE.
  
 PLAN SHEET M-202 & 203, NOTE FOR DRYER
 EXHAUST INDICATES 4" UP THRU ROOF W/WP
 CAP, INSECT SCREEN & B.D.D.DRYER EXHAUST
 IS TO BE "NON-SCREENED" WITH B.D.D.
 PLEASE CORRECT ALSO WORDING ON PLAN M204
  
 SHOW COMPLIANCE TO THE 2001 FBC(M) 303.4
 & 304.4, PROTECTION FOR EQUIPMENT IN
 PRIVATE GARAGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.