Plan Review Notes
Plan Review Notes For Permit 02041639
Permit Number 02041639
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-15 00:00:00~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~~
  
 PLEASE NOTE THE FOLLOWING
 DISCREPANCIES,CORRECT PLANS AND
 RESUBMIT FOR REVIEW.
  
 1} SIZE THE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66 NEC.
  
 2} ELECTRICAL PLAN SHOWS "MAIN
 DISC"OUTSIDE,"ELEC PANEL W/DISC"INSIDE
 AND THE RISER DIAGRAM SHOWS A MAIN
 DISCONNECT WITH A MLO PANEL.PLEASE
 REDRAW TO CLARIFY INTENT.
  
 3} THE PANEL SCHEDULE AND THE LOAD
 CALCULATIONS PANEL DO NOT CORRELATE.
  
 4} WASHER IS LISTED @ 3000W IN THE LOAD
 CALCULATIONS AND SHOWN ON A 20 AMP
 BREAKER WITH #12 CONDUCTORS ON THE
 PANEL SCHEDULE. PLEASE CLARIFY.
  
 5} THERE IS AN OVEN LISTED ON THE PANEL
 SCHEDULE BUT NOT IN THE LOAD
 CALCS.PLEASE CLARIFY.
  
 6} A/C #1 AHU @ 10K,THE BREAKER & BRANCH
 CIRCUIT CONDUCTORS ARE UNDERSIZED PER
 424-3(B).
  
 7} CAN'T DISCERN THE WALL LINE BETWEEN
 THE MASTER BED ROOM & THE W.I.C.,COMPLY
 WITH 210-52(A)(1).
  
 IF THERE ARE QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392