| Plan Review Notes For Permit 02041630 |
| Permit Number |
02041630 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-07-23 00:00:00 | ****************** UNSAT ************** | | | | | | ********** NOTE ************ | | | 3RD TIME UNSAT, PLEASE SEE ATTACHED | | | SHEET FOR FS.553.802B. PLANS BEING SENT | | | BACK FOR THE SAME COMMENTS. | | | PLEASE SEE ATTACHED SHEETS FOR PREVIOUS | | | TWO REVIEWS AND COMMENTS. | | | | | | 1)NOTE: PLEASE NOTE AN EQUIPMENT GROUND- | | | -ING CONDUCTOR IS STILL BEING SHOWN | | | BETWEEN METER AND MAIN?? THIS IS PARA- | | | LLELING THE NEUTRAL WHICH IS NOT | | | PERMITTED. PLEASE NOTE THAT THE NEUTRAL | | | IS BONDED WITH THE GRND SCREW AT THE | | | FIRST MEANS OF DISC. | | | | | | 2)NOTE: PLEASE NOTE THAT THE TWO SMALL | | | APPLIANCE CIRCUITS REQ`D PER 210-52B | | | 210-11-C-1 ARE STILL NOT SHOWN IN LOAD | | | CALCULATIONS?? PLEASE NOTE MICROWAVE IS | | | SHOWN ON LOAD CALCS BUT NOT PANEL | | | SCHEDULE? | | | | | | 3)NOTE: PLEASE VERIFY LOAD SHOWN FOR | | | RANGE AT 5KW? | | | | | | 4)NOTE: PLEASE NOTE SD IS SHOWN IN BATH, | | | SD`S ARE NOT PERMITTED IN BATHS PER | | | NFPA-72, 2-5.2.1.6 | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW AND | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | | | | BILL TROBAUGH | | | X-8392 |
|