| Plan Review Notes For Permit 02041552 |
| Permit Number |
02041552 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-17 00:00:00 | THE NORANDEX WINDOW DESIGN SHEET CITES | | | THE 1997 SBCCI CODE WHICH HAS BEEN | | | SUPERCEDED BY THE FBC 2001.PLEASE | | | REVISE AS NECESSARY AND ENSURE | | | COMPLIANCE WITH THE FBC. | | | | | | SHUTTERS FOR THE SECOND STORY ARE NOT A | | | PRACTICAL APPLICATION.PLEASE PROVIDE | | | AN ALTERNATE HURRICANE MISSILE IMPACT | | | RESISTANT METHOD.SEE THE ATTACHED | | | CITY IMPLEMENTATION STANDARD. | | | | | | SHEET 11 SECTION F, WRONGLY DEPICTS THE | | | FRT PLYWOOD ROOF SHEATHING TO BE | | | INSTALLED FOUR FEET FROM THE CENTER | | | LINE OF THE PARTY WALL.FBC 704.4.2 | | | (2) PROVIDES FOR THE PROTECTION TO | | | OCCUR FROM EACH "SIDE" OF THE WALL. | | | PLEASE REVISE AS NECESSARY. | | | | | | SHEET 11 SECTION B SHOWS A FOOTING DEPTH | | | OF 8" THAT SHOULD BE 12" IN ACCORDANCE | | | WITH FBC 1804.1.3. | | | | | | SHEET 11 SECTION C IS NOT CLEAR AS TO | | | HOW THE OVERHANG OUTLOOKER WILL BE | | | CONNECTED AND THE FEASIBILITY OF THE | | | VENTING IN THE SOFFIT. | | | | | | SBCCI REPORT #9755 FOR THE AMARR GARAGE | | | DOOR IS NOT A CURRENT LISTING WITH SBCCI | | | PLEASE PROVIDE A CURRENT OR ALTERNATE | | | LISTING. |
|