| Plan Review Notes For Permit 02041482 |
| Permit Number |
02041482 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-04 00:00:00 | *******************DENIED*************** | | | | | | MECHANICAL PERMIT 02041485 | | | | | | UNIT "C" - R | | | PLAN SHEET 17 SPLIT SYSTEM SCHEDULE | | | INDICATES 10 SEER FOR THE C.U., ENERGY | | | CALCS SHOW 11.0 SEER. | | | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | PRESSURE DIFFERNTIALS ACROSS CLOSED | | | DOORS WHERE RETURNS ARE CENTRALLY | | | LOCATED SHALL BE LIMITED TO .001" WC OR | | | LESS. PROVIDE AIR DUCT PATHWAYS OR AIR | | | TRANSFER PATHWAYS FROM THE HIGH PRESSURE | | | ZONE TO THE LOW ZONE. | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|