Plan Review Notes
Plan Review Notes For Permit 02041445
Permit Number 02041445
Review Stop P
Sequence Number 1
Notes
Date Text
2002-05-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 2, PER TABLE 403.1 TWO DRINKING
 FOUNTAINS ARE REQUIRED. SEE SEC 410.1
 2) SHT 4, HDCP SHOWER. PLEASE SHOW COM-
 PLIANCE FOR HDCP SHOWER PER SEC 11-4.21
 PROVIDE DETAILS FOR 11-4.21.2, 11-4.21.3
 11-4.21.4, 11-4.21.5, 11-4.21.6 AND 11-
 4.21.7
 3) SHT M1, WATER HEATER. PER SEC 504.7.1
 THE DISCHARGE PIPE SHALL NOT HAVE ANY
 TRAPPED SECTIONS AND SHALL HAVE A VISI-
 BLE AIR GAP OR AIR GAP FITTING LOCATED
 IN THE SAME ROOM AS THE WATER HEATER.
 4) SHT M1, WATER HEATER. PAN DRAIN SHALL
 BE A MINIMUM OF 3/4" AND SHALL BE IN-
 DIRECTLY DRAINED TO A FLOOR SINK NOT A
 FLOOR DRAIN.
 5) SHT M1, WATER ISOMETRIC. WATER HAMMER
 ARRESTORS ARE REQUIRED WHERE QUICK CLOS-
 ING VALVES ARE INSTALLED. (WASH MACHINES
 ICE MAKER, DISHWASHERS ECT., IF INSTALL-
 ED THEY SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT AT TOP
 OF THE DROP AS SHOWN.
 6) SHT M1, WATER ISOMETRIC. A MEANS OF
 CONTROLING THERMAL EXPANSION MAY BE RE-
 QUIRED PER SEC 607.3
 7) SHT 3, WATER HEATER SHALL BE PLACED
 SO AS TO PROVIDE AMPLE PROTECTION BET-
 WEEN THE APPLIANCE AND ADJACENT CONBUST-
 ABLE MATERIAL. NEC 422-17.
  
 REVIEW BY KEN STEVENS