Plan Review Notes For Permit 02041445
Permit Number 02041445
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-06 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
  
 2)NOTE: PLEASE NOTE THAT CIRCUIT #`S ON
 PLANS AND PANEL SCHEDULES NEED TO
 CORRELATE. PLEASE NOTE THAT THERE ARE
 CIRCUITS ON PLANS THAT ARE SHOWN AS
 "SPACE" ON SCHEDULE. THERE ARE CIRCUITS
 SHOWN ON PLANS THAT DO NOT FIGURE UP TO
 180VA FOR RECEPTS PER 220-3B-9
 PLEASE GO OVER PLANS AND CORRELATE AND
 LOAD CALCULATIONS NEED TO BE SHOWN NOT
 JUST CONNECTED LOADS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372