| Plan Review Notes For Permit 02041445 |
| Permit Number |
02041445 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-06 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE LOAD | | | CALCULATIONS NEED TO BE SHOWN. SQ FT/ | | | RECEPT LOADS ETC. PER 220-3,220-10, | | | 220-11, 220-13. (215-5) | | | | | | 2)NOTE: PLEASE NOTE THAT CIRCUIT #`S ON | | | PLANS AND PANEL SCHEDULES NEED TO | | | CORRELATE. PLEASE NOTE THAT THERE ARE | | | CIRCUITS ON PLANS THAT ARE SHOWN AS | | | "SPACE" ON SCHEDULE. THERE ARE CIRCUITS | | | SHOWN ON PLANS THAT DO NOT FIGURE UP TO | | | 180VA FOR RECEPTS PER 220-3B-9 | | | PLEASE GO OVER PLANS AND CORRELATE AND | | | LOAD CALCULATIONS NEED TO BE SHOWN NOT | | | JUST CONNECTED LOADS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|