| 2002-06-19 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-AFTER ORIGINAL DRAWINGS ARE CORRECTED |
| | BRING THEM TO PALM BEACH COUNTY TO PAY |
| | THE IMPACT FEES. BRING BACK STAMPED |
| | DRAWINGS AND PAID RECEIPT. |
| | 3-REVISE DWG A1. MIXING FBC 2001 AND SBC |
| | FOR 110MPH. SEE COMMENTS ON PLANS. |
| | ALSO, THERE AREN'T SLIDING GLASS DOORS |
| | ON THIS PROJECT. |
| | 4-REVISE ATTIC INSULATION VALUE. SEE THE |
| | ENERGY CALCULATIONS. |
| | 5-FOOTING F1 IS 16" DEEP. FBC 2001 SEC. |
| | 1804.1.3 REQUIRES 12" MINIMUM BELOW |
| | FINISHED GRADE. CLARIFY HOW IS THIS |
| | GOING TO BE ACHIEVED IF CONCRETE SLAB |
| | IS +/- 12" ABOVE GRADE. |
| | 6-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ROOF SHINGLES. |
| | B)FRENCH DOORS WITH LEGIBLE DRAWINGS. |
| | C)SINGLE HUNG WINDOWS WITH LEGIBLE DWGS. |
| | |
| | 7-STORM SHUTTERS: |
| | A)INSTALLATION SCHEDULE SUBMITTED DOES |
| | NOT MATCH ARCHITECTURAL PLANS. MISSING |
| | FRENCH DOORS. |
| | B)CLEARLY INDICATE ON STORM SHUTTERS |
| | MOUNTING CONDITIONS TO BE USED IN THIS |
| | PROJECT. |
| | CLEARLY INDICATE ON INSTALLATION |
| | SCHEDULE SPECIFIC ANCHOR AND SPACING |
| | TO BE USED ACCORDING TO THE MEAN ROOF |
| | HEIGHT, DESIGN PRESSURES, PANEL SPAN, |
| | CONNECTION TYPE, EDGE DISTANCE AND |
| | STRUCTURE TO BE ATTACHED TO. |