Notes
Date Text
2002-06-19 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-AFTER ORIGINAL DRAWINGS ARE CORRECTED
 BRING THEM TO PALM BEACH COUNTY TO PAY
 THE IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 3-REVISE DWG A1. MIXING FBC 2001 AND SBC
 FOR 110MPH. SEE COMMENTS ON PLANS.
 ALSO, THERE AREN'T SLIDING GLASS DOORS
 ON THIS PROJECT.
 4-REVISE ATTIC INSULATION VALUE. SEE THE
 ENERGY CALCULATIONS.
 5-FOOTING F1 IS 16" DEEP. FBC 2001 SEC.
 1804.1.3 REQUIRES 12" MINIMUM BELOW
 FINISHED GRADE. CLARIFY HOW IS THIS
 GOING TO BE ACHIEVED IF CONCRETE SLAB
 IS +/- 12" ABOVE GRADE.
 6-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF SHINGLES.
 B)FRENCH DOORS WITH LEGIBLE DRAWINGS.
 C)SINGLE HUNG WINDOWS WITH LEGIBLE DWGS.
  
 7-STORM SHUTTERS:
 A)INSTALLATION SCHEDULE SUBMITTED DOES
 NOT MATCH ARCHITECTURAL PLANS. MISSING
 FRENCH DOORS.
 B)CLEARLY INDICATE ON STORM SHUTTERS
 MOUNTING CONDITIONS TO BE USED IN THIS
 PROJECT.
 CLEARLY INDICATE ON INSTALLATION
 SCHEDULE SPECIFIC ANCHOR AND SPACING
 TO BE USED ACCORDING TO THE MEAN ROOF
 HEIGHT, DESIGN PRESSURES, PANEL SPAN,
 CONNECTION TYPE, EDGE DISTANCE AND
 STRUCTURE TO BE ATTACHED TO.