| 2002-07-16 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02041425 |
| | ADD: 9717 BAYWINDS DR |
| | CONT: SIERRA CONST |
| | TEL: (305) 216-7981 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | THIRD REVIEW |
| | |
| | 1) PLANS SUBMITTED AFTER THE FEB 28/2002 |
| | ARE TO BE DESIGNED TO THE 2001 FLORIDA |
| | BUILDING CODE. |
| | MANUFACTURED BUILDINGS- WHEN MANUFAC- |
| | TURED BUILDINGS ARE BUILT UNDER THE 1997 |
| | STANDARD BUILDING CODE AND THEY ARE THEN |
| | MOVED FROM THE ORIGINAL PLACEMENT AND |
| | PLANS ARE SUBMITTED, AFTER THE FEB 28, |
| | 2002 DEADLINE, THEY ALSO MUST CONFORM TO |
| | THE 2001 FLORIDA BUILDING CODE FOR WIND- |
| | ZONES, (140 MPH, 3 SECOND GUST), IN PALM |
| | BEACH COUNTY. |
| | THIS STRUCTURE WOULD BE OK TO PLACE |
| | IN A 110 MPH WIND ZONE. |
| | THE ENGINEER OF RECORD FOR THE MANU- |
| | FACTURED BUILDING COULD RECERTIFY THIS |
| | BUILDING FOR 140 MPH, 3 SECOND GUST, |
| | SHOW ENGINEERING FOR STRENGTHENING THE |
| | STRUCTURE TO 140 MPH. |
| | MANUFACTURED BUILDINGS- NEW CONSTRUC- |
| | TION, APPROVAL DATE ON THE LISTING |
| | AGENCY APPROVAL IS AFTER FEB 28,2002, |
| | THIS NEW STRUCTURE MUST ALSO COMPLY WITH |
| | THE WIND SPEED WHERE EVER THE UNIT IS TO |
| | BE PLACED WITHIN THE STATE. |
| | |
| | 2)FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH CO.,THE PERMIT PLANS STAMPED BY |
| | THEM AND THE RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. |