| Plan Review Notes For Permit 02041269 |
| Permit Number |
02041269 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-04 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1) FBC 1606.2.2.1THE DESIGN WIND | | | PRESSURES, ON THE ROOF FRAMING PLAN AND | | | GENERAL NOTES SHEET G1, HAVE BEEN | | | UNDERESTIMATED (REF FBC TABLE 1606.2B). | | | AMEND THE PRESSURES AND UPLIFTS AND | | | RESPECIFY THE TRUSS ANCHORS AS NECESSARY | | | TO DEMONSTRATE COMPLIANCE. | | | | | | 2) THE ATRIUM DOOR PRODUCT APPROVAL | | | NOTICE OF ACCEPTANCE NO. 01-0209.02 | | | EXPIRED PRIOR TO THE DATE OF APPLICATION | | | SUBMIT A CURRENT PRODUCT APPROVAL. | | | | | | 3) FIXED GLASS WINDOW PRODUCT APPROVAL | | | NOTICE OF ACCEPTANCE NO. 00-0512.02. | | | THE ASSOCIATED DRAWING SHEETS HAVE BEEN | | | UNNECESSARILY REDUCED DURING THE | | | COPYING PROCESS AND ARE NOT PROPERLY | | | LEGIBLE.SUBMIT LEGIBLE COPIES. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|