| 2002-05-28 00:00:00 | 2001 FLORIDA BUILDING CODE - MODEL D | | | | | | SHOW COMPLIANCE WITH 2001 FBC(M) 402.2.1 | | | OR TABLE 403.3. | | | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | PRESSURE DIFFERNTIALS ACROSS CLOSED | | | DOORS WHERE RETURNS ARE CENTRALLY | | | LOCATED SHALL BE LIMITED TO .001" WC OR | | | LESS. PROVIDE AIR DUCT PATHWAYS OR AIR | | | TRANSFER PATHWAYS FROM THE HIGH PRESSURE | | | ZONE TO THE LOW ZONE. | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | PLEASE NOTE IF DRYERS ARE GAS, SHOW | | | COMPLIANCE WITH 2001 FBC(M) 702. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|