| 2002-06-05 00:00:00 | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, THE PERMIT PLANS STAMPED |
| | BY THAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |
| | |
| | METRO DADE NOA 98-1110.06 IS EXPIRED. |
| | |
| | THE TRUSSES ARE DESIGNED TO THE 1997 |
| | STANDARD BUILDING CODE, THEY ARE |
| | REQUIRED TO COMPLY WITH THE 2001 FBC. |
| | PLEASE REVISE AS NECESSARY. |
| | |
| | THE ENGINEER OF RECORD IS REQUIRED TO |
| | REVIEW THE DELEGATED DESIGN AREAS SUCH |
| | AS THE TRUSSES AND THE PRE-CAST WALL |
| | SYSTEM.PROVIDE DOCUMENTATION THAT THIS |
| | HAS BEEN DONE. |
| | |
| | THE ROYALL WALL PLANS DO NOT INDICATE |
| | THE SPECIFIC PROJECT OR CALCULATIONS. |
| | SEE RULE 61G15-31 OF THE FAC. |
| | |
| | THE ROYALL WALL PLANS DO NOT REFLECT |
| | THE DESIGN CRITERIA OF ACI 318-99 IN |
| | ACCORDANCE WITH FBC 1918.1 OR THE WIND |
| | DESIGN INFORMATION AS PROVIDED FOR IN |
| | FBC 1606. |
| | |
| | THE ENGINEER OF RECORD HAS NOT |
| | SPECIFIED ANY DESIGN CRITERIA FOR THE |
| | DELEGATED ENGINEERING DESIGN AS |
| | PROVIDED FOR IN 61G15-30.IN FACT, THE |
| | PLANS SHEETS ARE NOT EVEN NUMBERED.SEE |
| | ALSO, 61G15-30.003 RE: DOCUMENT |
| | CLASSIFICATION |
| | |
| | PROVIDE FOR TERMITE PROTECTION IN |
| | ACCORDANCE WITH FBC 1816.1.7. |
| | |
| | SHOW THE INTERNAL PRESSURE COEFFICIENT |
| | AND COMPONENT & CLADDING PRESSURES FOR |
| | THE ROOF COVERING.SEE FBC 1606.1.7. |