| Notes |
| Date |
Text |
| 2002-05-01 00:00:00 | ~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~ | | | | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATIONAND MAKE ANY NECESSARY | | | CHANGES TO THE PLANS AND RESUBMIT FOR | | | REVIEW: | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | 2} PLEASE NOTE MISSING DISCONNECT | | | FOR A/C CONDENSOR,MUST CONFORM TO | | | 440-14NEC. | | | | | | 3}PLEASE NOTE THAT ALL PLANS | | | THAT ARE SIGNED AND SEALED BY ARCH/ OR | | | ENGINEER ARE REQ`D PER 61G15-23.002 FOR | | | ENGINEER AND 61G1-16.004 FOR ARCH.(TITLE | | | BLOCK). | | | | | | 4}PLEASE LIST THE REQ`D ARC | | | FAULT PROECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12 | | | | | | | | | 5} RECEPTACLE SPACING TO COMPLY WITH ART | | | ICLE 210-52(A). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 |
|