| Plan Review Notes For Permit 02041152 |
| Permit Number |
02041152 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BLDG CHAPTER 11 | | | | | | 1) SHTS A-1 & P-2.1 DOOR SHALL NOT OPEN | | | INTO CLEAR FLOOR SPACE OF AND ACCESSIBLE | | | FIXTURE. | | | 2) FBC PLMG TABLE REQUIRES A DRINKING | | | FOUNTAIN & AND A SERVICE SINK. PLEASE | | | PROVIDE REQUIRED FIXTURES. | | | 3) SHT P0.1 PLUMBING NOTES #23, CONDEN- | | | SATE LINES AS SHOWN ON SHT P2.1 FBC SEC | | | 1503.4.4 REQUIRES THAT DISCHARGE FROM | | | CONDENSATE BE MINIMUM OF 12" FROM BLDG. | | | 4) SHT PO.1 PLUMBING NOTES #13 AIR CHAM- | | | BERS NOT APPROVED, DELETE REFERENCE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|